Application example analysis of medical power supply
There have been customers bought a low-cost medical grade UPS , the power supply is 5V 200mA, hundreds of batches of the unit price is $5. The device sells tens of thousands of dollars. The surprisingly low price of power seems pretty good. After opening this power supply, it is found that it has only one single-sided printed circuit board. In order to save the cost, the circuit board has no metallized through-hole. The circuit board adopts the surface mounting structure, and the component density is very large. The component spacing does not meet the requirements and design criteria of creepage distance specified by medical power supply and related safety management institutions. Leakage current up to 900mA, far beyond the specification limit. The creepage distance and the gap voltage can not reach the voltage used in the general power supply. The spacing between the high pressure regions is only 0.5mm, and the flux resistance is used to improve the dielectric resist...